Input (DC)
Max. PV input voltage1500 V
Min. PV input voltage / Startup input800 V / 840 V
MPP voltage range for nominal power800 – 1300 V
No. of independent MPP inputs1
No. of DC inputs18 – 28
Max. PV input current3508 A
Max. DC short-circuit current4210 A
PV array configurationNegative Grounding
Output (AC)
Nominal AC power (at 55 ˚C)2500 kW
Max. AC output power at PF=1 (at 50 ˚C)2750 kW
Max. AC apparent power (at 50 ˚C)2750 kVA
Max. AC output current2886 A
Nominal AC voltage550 V
AC voltage range495 – 605 V
THD< 3 % (at nominal power)
DC current injection< 0.5 % In
Power factor at nominal power / Adjustable power factor> 0.99 / 0.8 leading – 0.8 lagging
Feed-in phases / Connection phases3 / 3
Nominal grid frequency / Grid frequency range50 Hz / 45 – 55 Hz, 60 Hz / 55 – 65 Hz
Efficiency
Max. efficiency / CEC efficiency98.8 % / 98.5 %
Protection
DC input protectionLoad switch + fuse
AC output protectionCircuit breaker
Overvoltage protectionDC Type II / AC Type II
Grid monitoring / Ground fault monitoringYes / Yes
Overheat protectionYes
Insulation monitoringOptional
General Data
Dimensions (W*H*D)2991*2896*2438 mm 117.76"*114.0"*96.0"
Weight6.9 T 15211.9 lb
Isolation methodTransformerless
Degree of protectionNEMA 3R
Night power consumption220/110Vac, 5 kVA / Optional: 480 Vac, 30 kVA
Operating ambient temperature range-30 to 60 °C(> 50 °C derating) -22 to 140 °F (> 122 °F derating)
Allowable relative humidity range (non-condensing)0 - 95 %
Cooling methodTemperature controlled forced air cooling
Max. operating altitude4000 m(> 2000 m derating) 13123 ft (> 6561 ft derating)
DisplayTouch screen
CommunicationStandard: RS485, Ethernet; Optional: optical fiber
ComplianceUL 1741, IEEE 1547, UL1741 SA, NEC Standard
Grid supportNight SVG function (optional), L/HVRT, L/HFRT, active & reactive power control and power ramp rate control
Transformer