| Input (DC) |
| Max. PV input voltage | 1500 V |
| Min. PV input voltage / Startup input | 800 V / 840 V |
| MPP voltage range for nominal power | 800 – 1300 V |
| No. of independent MPP inputs | 1 |
| No. of DC inputs | 18 – 28 |
| Max. PV input current | 3508 A |
| Max. DC short-circuit current | 4210 A |
| PV array configuration | Negative Grounding |
| Output (AC) |
| Nominal AC power (at 55 ˚C) | 2500 kW |
| Max. AC output power at PF=1 (at 50 ˚C) | 2750 kW |
| Max. AC apparent power (at 50 ˚C) | 2750 kVA |
| Max. AC output current | 2886 A |
| Nominal AC voltage | - |
| AC voltage range | 10 – 35 kV |
| THD | < 3 % (at nominal power) |
| DC current injection | < 0.5 % In |
| Power factor at nominal power / Adjustable power factor | > 0.99 / 0.8 leading – 0.8 lagging |
| Feed-in phases / Connection phases | 3 / 3 |
| Efficiency |
| Max. efficiency / CEC efficiency | 98.8 % / 98.5 % |
| Protection |
| DC input protection | Load switch + fuse |
| AC output protection | Circuit breaker |
| Overvoltage protection | DC Type II / AC Type II |
| Grid monitoring / Ground fault monitoring | Yes / Yes |
| Overheat protection | Yes |
| General Data |
| Dimensions (W*H*D) | 6058*2896*2438 mm 238.5''*114.0''*96.0'' |
| Weight | 15.7 T 34612.6 lb |
| Isolation method | - |
| Degree of protection | NEMA 3R |
| Night power consumption | - |
| Operating ambient temperature range | -30 to 60 ℃ (> 50 ℃ derating) -22 to 140 ℉(> 122 derating) |
| Allowable relative humidity range (non-condensing) | 0 – 95 % |
| Cooling method | Temperature controlled forced air cooling |
| Max. operating altitude | 1000 m (standard) / > 1000 m (optional) 3280.8 ft(standard) / > 3280.8 (optional) |
| Display | Touch screen |
| Communication | Standard: RS485, Ethernet; Optional: optical fiber |
| Compliance | UL 1741, IEEE 1547, UL1741 SA, NEC Standard |
| Grid support | Night SVG function (optional), L/HVRT, L/HFRT, active & reactive power control and power ramp rate control |
| Transformer |